Lightning Risk Calculator Tool

Lightning Risk Analysis Program

Protection Level Selection - NFC 17-102 Standard
Risk Assessment According to IEC 62305 / TS EN 62305 Standard

Building Dimensions

meters
meters
meters

Environmental Coefficient (C1)

Structural Coefficient (C2)

Select the value from the table below based on roof and building material:

Roof / Structure Metal Tile Flammable
Metal 0.5 1.0 2.0
Tile 1.0 1.0 2.5
Flammable 2.0 2.5 3.0

Selected C2 Value: -

Building Content Coefficient (C3)

Human Density Coefficient (C4)

Building Importance in the Area (C5)

Thunderstorm Days (Nk)

Select according to your region from the Turkey Thunderstorm Map below.
Turkey Thunderstorm Map

Calculation Results

Effective Equivalent Area (Ae)
-
Lightning Density (Ng)
-
strikes/km²/year
Expected Lightning (Nd)
-
strikes/year
Total Coefficient (C)
-
C2×C3×C4×C5
Approved Lightning (Nc)
-
strikes/year
Efficiency (E)
-
1-(Nc/Nd)

-

-

-

Mesh Size
-
Down Conductor Spacing
-
Rolling Sphere Radius
-

Protection Level Reference Table

Efficiency (E) Protection Level Mesh Size Down Spacing Rolling Sphere Radius = r
E > 0.98 Level I + Additional Measures 5×5 m² 10 20 m
0.95 < E ≤ 0.98 Seviye I (LPL1) 5x5 m² 10 20 m
0.90 < E ≤ 0.95 Seviye II (LPL2) 10x10 m² 10 30 m
0.80 < E ≤ 0.90 Seviye III (LPL3) 15x15 m² 15 45 m
E ≤ 0.80 veya Nd ≤ Nc Seviye IV (LPL4) 20×20 m² 20 60 m

Note: IF Nd ≤ Nc, PROTECTION IS OPTIONAL.
IF Nd > Nc, PROTECTION IS REQUIRED. In this case; Efficiency, E=1-(Nc/Nd) calculated value determines the PROTECTION LEVEL.

Active Lightning Rod Selection Tables

Active lightning rods provide a wider protection area compared to standard rod lightning conductors. The tables below show the protection radius (Rp) in meters based on building height and protection level.

Piezoelectric Crystal Active Lightning Rod Selection Table

H(m) ΔT=15μs ΔT=30μs ΔT=45μs ΔT=60μs
I II III IV I II III IV I II III IV I II III IV
213151820192225282528323631353943
425303641384451575157647263697885
5323745514855637163718189798697107
6323846524855647263718190798797107
8333947544956657364728291798798108
10344049564957667564728392798899109
203544556350597181657486978089102113
3035455869506073856575891018090104116
6035456075506075906575901058090105120

Electrostatic Active Lightning Rod Selection Table

H(m) ΔT=30μs ΔT=45μs ΔT=60μs
I II III IV I II III IV I II III IV
2192225282528323631353943
4384451575157647263697885
54855637163718189798697107
64855647263718190798797107
84956657364728291798798108
104957667564728392798899109
2050597181657485978089102113
30506073856575891018090104116
60506075906575901058090105120

Note: Table values show the protection radius (Rp) in meters.
ΔT: Early conductivity time (μs - microsecond)
H: Lightning rod installation height (meters)

Logo
ESCO ELEKTRİK
www.escoelektrik.com
info@escoelektrik.com
+90 (216) 471 81 66
LIGHTNING RISK ASSESSMENT
Protection Level Selection - NFC 17-102 / IEC 62305 / TS EN 62305
FORMULA VALUES RESULT
Ae = LxW + 6xH(L+W) + 9πH² L=-m, W=-m, H=-m Ae = -
Ng = 0.04 x Td^1.25 Td = - Ng = -
Nd = Ae x Ng x C1 x 10⁻⁶ C1 = - Nd = -
C = C2 x C3 x C4 x C5 C2=-, C3=-, C4=-, C5=- C = -
Nc = 5.5 x 10⁻³ / C Nc = -
E = 1 - (Nc / Nd) E = -
PROTECTION REQUIRED
-
Mesh: -
Down: -
Sphere: -
PROTECTION LEVEL
E Protection Level Mesh Down r
>0.98I+Ek5×51020
0.95-0.98I5×51020
0.90-0.95II10×101030
0.80-0.90III15×151545
≤0.80IV20×202060
PIEZOELECTRIC ACTIVE LIGHTNING ROD (Rp meters)
H ΔT=15μs ΔT=30μs ΔT=45μs ΔT=60μs
I II III IV I II III IV I II III IV I II III IV
213151820192225282528323631353943
425303641384451575157647263697885
5323745514855637163718189798697107
6323846524855647263718190798797107
8333947544956657364728291798798108
10344049564957667564728392798899109
203544556350597181657486978089102113
3035455869506073856575891018090104116
6035456075506075906575901058090105120
ELECTROSTATIC ACTIVE LIGHTNING ROD (Rp meters)
H ΔT=30μs ΔT=45μs ΔT=60μs
IIIIIIIV IIIIIIIV IIIIIIIV
2192225282528323631353943
4384451575157647263697885
54855637163718189798697107
64855647263718190798797107
84956657364728291798798108
104957667564728392798899109
2050597181657485978089102113
30506073856575891018090104116
60506075906575901058090105120
For projects with Level I + Additional Measures protection level, please contact our business development department.
This report was generated by ESCO Electric Lightning Risk Analysis Program. | Date: -
WhatsApp