Lightning Risk Analysis Program
Protection Level Selection
Expected lightning frequency (Nd), acceptable frequency (Nc) and efficiency (E) are calculated from the building data.
- NF C 17-102:1995 — Nc = 0.0055 / (C2 × C3 × C4 × C5). Current method, default.
- NFPA 780 — Nc = 0.0015 / (C2 × C3 × C4 × C5).
Protection level I–IV thresholds remain the thresholds already used in this calculator. They do not change with the selected standard.
These options represent the simplified Nc methods of the related standards. They do not mean that the calculator as a whole conforms to NFPA 780, NF C 17-102:1995 or IEC 62305 / TS EN 62305.
Calculation Standard
Building Dimensions
Environmental Coefficient (C1)
Structural Coefficient (C2)
Select the value from the table below based on roof and building material:
| Roof / Structure | Metal | Tile | Flammable |
|---|---|---|---|
| Metal | 0.5 | 1.0 | 2.0 |
| Tile | 1.0 | 1.0 | 2.5 |
| Flammable | 2.0 | 2.5 | 3.0 |
Selected C2 Value: -
Building Content Coefficient (C3)
Human Density Coefficient (C4)
Building Importance in the Area (C5)
Thunderstorm Days (Nk)
Calculation Results
-
-
Protection Level Reference Table
| Efficiency (E) | Protection Level | Mesh Size | Down Spacing | Rolling Sphere Radius = r |
|---|---|---|---|---|
| E > 0.98 | Level I + Additional Measures | 5×5 m² | 10 | 20 m |
| 0.95 < E ≤ 0.98 | Seviye I (LPL1) | 5x5 m² | 10 | 20 m |
| 0.90 < E ≤ 0.95 | Seviye II (LPL2) | 10x10 m² | 10 | 30 m |
| 0.80 < E ≤ 0.90 | Seviye III (LPL3) | 15x15 m² | 15 | 45 m |
| E ≤ 0.80 veya Nd ≤ Nc | Seviye IV (LPL4) | 20×20 m² | 20 | 60 m |
Note: IF Nd ≤ Nc, PROTECTION IS OPTIONAL.
IF Nd > Nc, PROTECTION IS REQUIRED. In this case; Efficiency, E=1-(Nc/Nd) calculated value determines the PROTECTION LEVEL.
Active Lightning Rod Selection Tables
Active lightning rods provide a wider protection area compared to standard rod lightning conductors. The tables below show the protection radius (Rp) in meters based on building height and protection level.
Piezoelectric Crystal Active Lightning Rod Selection Table
| H(m) | ΔT=15μs | ΔT=30μs | ΔT=45μs | ΔT=60μs | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| I | II | III | IV | I | II | III | IV | I | II | III | IV | I | II | III | IV | |
| 2 | 13 | 15 | 18 | 20 | 19 | 22 | 25 | 28 | 25 | 28 | 32 | 36 | 31 | 35 | 39 | 43 |
| 4 | 25 | 30 | 36 | 41 | 38 | 44 | 51 | 57 | 51 | 57 | 64 | 72 | 63 | 69 | 78 | 85 |
| 5 | 32 | 37 | 45 | 51 | 48 | 55 | 63 | 71 | 63 | 71 | 81 | 89 | 79 | 86 | 97 | 107 |
| 6 | 32 | 38 | 46 | 52 | 48 | 55 | 64 | 72 | 63 | 71 | 81 | 90 | 79 | 87 | 97 | 107 |
| 8 | 33 | 39 | 47 | 54 | 49 | 56 | 65 | 73 | 64 | 72 | 82 | 91 | 79 | 87 | 98 | 108 |
| 10 | 34 | 40 | 49 | 56 | 49 | 57 | 66 | 75 | 64 | 72 | 83 | 92 | 79 | 88 | 99 | 109 |
| 20 | 35 | 44 | 55 | 63 | 50 | 59 | 71 | 81 | 65 | 74 | 86 | 97 | 80 | 89 | 102 | 113 |
| 30 | 35 | 45 | 58 | 69 | 50 | 60 | 73 | 85 | 65 | 75 | 89 | 101 | 80 | 90 | 104 | 116 |
| 60 | 35 | 45 | 60 | 75 | 50 | 60 | 75 | 90 | 65 | 75 | 90 | 105 | 80 | 90 | 105 | 120 |
Electrostatic Active Lightning Rod Selection Table
| H(m) | ΔT=30μs | ΔT=45μs | ΔT=60μs | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| I | II | III | IV | I | II | III | IV | I | II | III | IV | |
| 2 | 19 | 22 | 25 | 28 | 25 | 28 | 32 | 36 | 31 | 35 | 39 | 43 |
| 4 | 38 | 44 | 51 | 57 | 51 | 57 | 64 | 72 | 63 | 69 | 78 | 85 |
| 5 | 48 | 55 | 63 | 71 | 63 | 71 | 81 | 89 | 79 | 86 | 97 | 107 |
| 6 | 48 | 55 | 64 | 72 | 63 | 71 | 81 | 90 | 79 | 87 | 97 | 107 |
| 8 | 49 | 56 | 65 | 73 | 64 | 72 | 82 | 91 | 79 | 87 | 98 | 108 |
| 10 | 49 | 57 | 66 | 75 | 64 | 72 | 83 | 92 | 79 | 88 | 99 | 109 |
| 20 | 50 | 59 | 71 | 81 | 65 | 74 | 85 | 97 | 80 | 89 | 102 | 113 |
| 30 | 50 | 60 | 73 | 85 | 65 | 75 | 89 | 101 | 80 | 90 | 104 | 116 |
| 60 | 50 | 60 | 75 | 90 | 65 | 75 | 90 | 105 | 80 | 90 | 105 | 120 |
Note: Table values show the protection radius (Rp) in meters.
ΔT: Early conductivity time (μs - microsecond)
H: Lightning rod installation height (meters)